Rosslare AC-215 Installation Guide Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 39
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
AC-215 Single and Double Door Access Control Unit
Hardware Installation Guide
12
The following lists switch 1 and 2 status and baud rate:
Switch 1 Switch 2 Baud Rate
Off
Off 9600
Off
On 19200
On
Off 38400
On
On 56000
! The ACU baud rate must be identical to the host PC’s serial port baud rate
ACU Type
The ACU type is defined using the third dipswitch. Both the single and double can be set.
! Off - defines single door controls
! On - defines a double door controls
Single Door Controller
This access type has two readers, IN and OUT, as follows:
Outputs: Door lock strike
Auxiliary output
Alarm output
General purpose output
Inputs: Release to exit
Door monitor input
Tamper input
General purpose input
! For more information refer to the Input Output chapter, page 7.
1 2 3 4 5 6 7 8
Page view 18